Je bent hier:

Transformer Oil IEC 60296 inhibited 21023

MAXOLINE Transformer Oil IEC 60296:2003 21023 is a well refined, naphthenic mineral insulating oil inhibited. Suitable for use in transformers of all categories as well as for other electrical equipment such as circuit breakers or tap changers.
MAXOLINE Transformer Oil IEC 60296 “Inhibited” meets the general requirements of Table 3 for mineral insulating oils for transformers and switchgears of the IEC 60296: 2020 (Table 3) and the specific requirements of chapter 7.1 relating to a higher oxidation stability and a low sulfur content.

MAXOLINE Transformer Oil IEC 60296 Inhibited is analytically proved non corrosive and does not contain DBDS, no passivators and no pour point depressants. StaSo Transformer Oil I is characterized by a very good low-temperature performance, excellent oxidation stability and gets delivered dried with a very high breakdown voltage.

Article number

CAAZ202/21023

H.S.Code

27.10.19.93

Viscosity 40 °C mm²/s

Max 12,0

Viscosity -30 °C mm²/s

Max 1800

Performance Level

IEC 60296:2020 5.1.4

Pour Point °C

-40

Water content mg/kg IEC 60814

Max 40

Breakdown Voltage IEC 60156

– Before treatment Min 30
– After treatment Min 70

Density, 20 °C kg/m3 ISO 12185

Max 895

DDF 90 °C IEC 60247

Max 0,005

The data published are to our best knowledge the correct information. We reserve the right to alter the specifications any time and without prior notice.